Java Games: Flashcards, matching, concentration, and word search.

Flash Cards

These flash cards will help you identify KEY WORDS in a Code section.

AB
school general lighting load3va
minimum size overhead service drop#8 or larger
circuit breaker ON isUP position
smallest grounding electrode#8
minimum size for grounding instrument transformers#12 CU. #10 AL.
circuit breaker as a switchSWD
copper buss bar1000 amperes per Sq. In.
aluminum buss bar700 amperes per Sq. In.
bushing fiber or plastic#4 or larger conductor
air conditioner hard wiredover 250 volts
air conditioner room 120 volts10' cord max
air space in a wet location1/4"
NM ampacity60c
fixture over bath tub8'
no overcurrent devicesbathroom
no overcurrent devicesclothes closet
binding screw or stud#10 or smaller
bonding jumper TV, communication#6
combustible wall set back0"
non-combustible wall set back1/4"
length of conductor in a box6"
dwelling unit outlets12' spacing no more than 6' from an outlet
non dwelling unit outlet rating180 va
angle pull6 times
straight pull8 times
branch ckt. outdoor overheadmin #10 50' or less
continuous loads125%
fixture socket maximum weight6 lbs.
direct buried cableprotected not more than 18" below grade
Class 1 locationsFlammable gases, vapors, liquids
Class 2 locationscombustible dust
Class 3 locationsignitible fibers, flyings
Class 1 remote control and signaling ckts.not over 600 volts
Class 1 sealing compound5/8" thick min.
not standard fuse55 amperes
not standard circuit breaker550 amperes
co-ax cable voltage60 volts max
bonding grid for pool#8 solid
CATV bonding jumper#6
Commercial garage floor areaClass 1 Division 2
communication drop over flat roof8'
conductors considered outside of the building2" concrete
conductors in plenumsnot NM (Romex)
conduit bodies (LBs)accessible
conduit on washed walls1/4" air space
conduit nipples 24" or less60% fill
# of conductors in pipe 153%
# of conductors in pipe 231%
# of conductors in pipe over 240%
AC disconnectwithin sight or lockable
motor disconnectwithin sight or lockable
bare copper concentricUSE cable
outlet in crawl spaceGFCI protected
outdoor outletsGFCI protected
within 6' of a sinkGFCI protected
within 3' of bathroom basinGFCI protected
garage outlets dwelling unitGFCI protected
kitchen counter top outletsGFCI protected
boat housesGFCI protected
commercial kitchens 15, 20a outletsGFCI protected
outdoorsGFCI protected
bathroom commercialGFCI protected
rooftopsGFCI protected
nurse call systemcritical branch circuit
physical damageschedule 80 PVC
transformer vault damper1 1/2 hrs. rated
holiday lighting90 days
damp locationprotected from the weather
heater elements sub divided48 amps/ 60 OCP
OCPover current protection
elevator lightingseparate circuit
dwelling unit outlet load0 va included in general lighting
#18 ga fixture wire6 amperes
#16 ga fixture wire8 amperes
#14 ga fixture wire17 amperes
#12 ga fixture wire23 amperes
#10 ga fixture wire28 amperes
emergency back up10 seconds
legally required back up60 seconds
optional back upno time limit
elevator parallel conductorsmallest #20 ga
parallel conductor building wire1/0 smallest
equipment terminal 100 amperes or more75c rated
equipment terminals less than 100 amperes60c rated
ceiling outlet boxup to 50 lbs.
#8 FEPB Cu.80 amperes
volume allowance #181.5 Cu. In.
volume allowance #161.75 Cu. In.
volume allowance #142.00 Cu. In.
volume allowance #122.25 Cu. In.
volume allowance #102.5 Cu. In.
volume allowance #83.00 Cu. In.
volume allowance #65.00 Cu. In.
festoon lightingoutdoor
bathroom floor heatedGFCI protected
ground rod length8'
GFInot in bedroom
240v exposed live parts both sides3'
service not over 300v12' above driveway
free conductor at boxes6"
insulation high heat wet locationTHHW
insulation high heat wet nylon coverTHWN
Aluminum rigid sizes1/2" thru 6"
rigid conduit maximum bends4 quarter bends
runnung threadsnot allowed
CO/ALRfor Aluminum connections
Code letter "P"motors marked 12.5 Kva
three phase overloadsone for each phase
seal offsminimize passage of gases, vapors and flames
sign in wet location1/4" drain holes
communication wire separated from building wires4"
1/0 bare.109 sq in
#126530 cm
#2 XHHW-266360
#2 bare.067 sq in
transformer with askarel6" to combustible materials
service conductors 30" downwarning tape 12" above
#14s in a 3X2X2 box5
#12s in a 3X2X2 box4
4X4X1-1/2" box21 cu in
#12s in a 100X54X48 box5
Control circuit devices with screw-type pressure terminals used with 14 AWG or smaller copper conductors shall be torqued to a minimum of7 lb-in
Capable of being removed or exposed without damaging the building structure or finish or not permanently closed in by the structure or finish of the building.Accessible (as applied to wiring methods)
An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.Authority Having Jurisdiction (AHJ)
All circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device. (Feeder
The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).Branch Circuit
A system or circuit conductor that is intentionally grounded.Grounded Conductor
Where this Code specifies that one equipment shall be “in sight from,” “within sight from,” or “within sight of,” and so forth, another equipment, the specified equipment is to be visible and not more than 15 m (50 ft) distant from the other.In Sight From (Within Sight From, Within Sight)
A location not normally subject to dampness or wetness. A location classified as dry may be temporarily subject to dampness or wetness, as in the case of a building under construction.Location, Dry
Installations underground or in concrete slabs or masonry in direct contact with the earth; in locations subject to saturation with water or other liquids, such as vehicle washing areas; and in unprotected locations exposed to weather.Location, Wet
Locations protected from weather and not subject to saturation with water or other liquids but subject to moderate degrees of moisture.Location, Damp
A point on the wiring system at which current is taken to supply utilization equipment.Outlet
One who has skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training to recognize and avoid the hazards involved.Qualified Person
Constructed or protected so that exposure to a beating rain will not result in the entrance of water under specified test conditions.Raintight
RainproofConstructed, protected, or treated so as to prevent rain from interfering with the successful operation of the apparatus under specified test conditions.
The written consent of the authority having jurisdiction.Special Permission.
Constructed so that moisture will not enter the enclosure under specified test conditions.Watertight
Constructed or protected so that exposure to the weather will not interfere with successful operation.Weatherproof
Enclosures constructed so that dust will not enter under specified test conditions.Dusttight
Type of protection where any spark or thermal effect is incapable of causing ignition of a mixture of flammable or combustible material in air under prescribed test conditionsIntrinsic Safety “i”.